The rule this planner uses
Stored energy is amp-hours times 12.8 V, even when the bank is 24 V or 48 V, so the chargers are compared on the same watt-hours. 200 Ah at 12.8 V is 2,560 Wh. Under that, the alternator-side charger is 30 A. At that and above, it is 50 A. Watt-hours per hour of driving come from the charger's output, not from a 50 A label times the bank voltage.
| Stored energy | Charger | Per hour of driving |
|---|---|---|
| Under 2,560 Wh | 30 A on 12 V | about 390 Wh |
| 2,560 Wh and up | 50 A on 12 V | about 650 Wh |
| 24 V bank, 2,560 Wh and up | 50 A on the alternator side | about 700 Wh |
| 48 V bank | Orion-Tr Smart 12/48-8A, 8 A | about 380 Wh |
On 12 V, 30 A times 13 V is about 390 Wh an hour, and 50 A times 13 V is about 650 Wh an hour. That 13 V is the same planning voltage the alternator page uses. A 50 A 12 V charger in this class is the Victron Orion XS 12/12-50. Its manual is the Orion XS 12/12-50 DC-DC charger manual. The 390 and 650 Wh figures are this planner's, from amps times 13 V, not a second rating printed here.
On 24 V the 50 A figure is still the alternator side. The planner counts 50 A times 14 V, about 700 Wh an hour. Explorist and Victron describe that 12 V input case as about 700 W, not 50 A times 24 V.
On 48 V the planner uses one Victron Orion-Tr Smart 12/48-8A. The 380 W figure is that charger's continuous output at 40°C, from the Victron datasheet. It is about 380 Wh per hour of driving, whatever a 50 A label used to suggest. A second unit in parallel is a separate choice, because it asks the 12 V alternator for more current.
Worked sample (planning estimates)
The two-person remote-work bank is 500 Ah at 12 V, 6,400 Wh. That is over 2,560 Wh, so the planner picks 50 A. About 650 Wh comes back per hour of driving. About 51 A lands in the bank, within half of 500 Ah. This planner treats half the amp-hour rating as a usual lithium charge rate. Over that, it says so, and you can still keep the charger.
A 100 Ah 12 V bank is 1,280 Wh, under the step, so it stays on the first row of the table: 30 A on 12 V, about 390 Wh. That is a slower refill than the 50 A row.
What it depends on
The charger size is not the whole question. Will the alternator keep up depends on the alternator's rating, what the van already uses, idle versus highway, heat, and whether the alternator is the variable-voltage kind that needs a charger mode or an ignition signal.
- Input versus output. The charger's rating is its output. It pulls more than that from the van.
- The cable run. A long run from the starter battery can drop the voltage until the charger cuts back. The manual sets the cable and the fuse.
- Solar beside it. A roof that already covers the day does not need a bigger charger. A winter day that solar cannot cover is where the hour of driving matters. Solar sizing.
- The inverter. This charger refills the bank. The inverter is sized from the AC loads, not from these amps. What size inverter a van needs.
- Two chargers. Stacking two 50 A chargers, or two Orion-Tr units, is a different draw. If the sum sits near the alternator's rating, size down or ask the van maker's upfitter support what the alternator is meant to carry.
First numbers states the charger amps next to the battery size for the van and the loads you enter.
When to bring in a professional
The run from the starter battery carries high current in the engine bay, with fuses at both ends per the charger manual. Where you are allowed to tap the van's electrical system depends on the van maker's guidance. Have a qualified electrical tech or upfitter design or check this run before you connect it.